Steel Wrapped Calcium Sulphate System
Specifications » Steel Wrapped Calcium Sulphate System

Recommended Applications
|
SYSTEM NAME Steel Wrapped Calcium Sulphate System
SYSTEM CODE SW-CS
COMPLIANT STANDARDS Australian Standard AS4154 / AS4155 Australian Standard AS1170 CISCA Standard UFGS - 09 69 11/15 PSA MOB PF2 1992 NATA Testing Certification IS09239 - 1 -2003 EN12825 - 2001 DIN4102- 1 -1998 |
DESCRIPTION The Steel Wrapped Calcium Sulphate System has been designed for general office areas such as commercial complexes, banks, libaries and learning institutions where the space is occupied by workstations and office equipment. |
Specifiers Guide

The adjacent table details how to nominate the ASP Calcium Sulphate System in your project specification.
Access Floor Panel
|
|
Type: SW Series - Steel Wrapped Size: The panels are 600mm x 600mm in size and are interchangeable with other panels. Depth: 30mm Construction: The panel is constructed from a lower sheet of die formed steel with corrosion resistant protection, inside and out, encapsulating a calcium sulphate core placed in the lower case. A top sheet of steel is then positioned and the edges are flowed and pressed to overlap the lower case. Core: Calcium Sulphate Tolerance: ±0.25mm and a flatness tolerance of ±0.5mm measured on a diagonal across the top of the panel Finish: Galvanized steel. Connection: The panel is screw fixed to the pedestal head at all four corner
|
Panel Load Tolerances
AUSTRALIAN STANDARD (AS)
Safety Factor: Panels must provide a minimum safety factor of 3 times the concentrated load specified above in accordance with AS4154-1993.
CISCA STANDARD

Safety Factor: Panels must provide a minimum safety factor of 5 times the uniform load specified above in accordance with ICC-ES AC300.
PSA MOB STANDARD

Safety Factor: Panels must provide a minimum safety factor of 3 times the concentrated load specified above in accordance with PSA MOB PF2 1992.
Access Floor Pedestals
|
|
Size: 10,000mm² base plate
Locking: The pedestals will be provided with an adjusting and locking nut to maintain the assembly at a selected height, which requires a deliberate action to change the height setting, and which prevents vibration displacement.
Finish: ASP’s standard powder coated finish.
Connection: The panel is either gravity laid or screw fixed to the pedestal head at all four corners. For finished floor heights over 800mm a rigid grid system with stringers is used.
Finished Floor Height (FFH): The finished floor height of the access floor is measured from the sub-floor to the top surface of the installed access floor.
|
Access Floor Stringers
|
|
Type: WG6 Stringer Size: 600mm Construction: The steel stringers shall be 31mm x 21mm x 1.4mm rectangular welded tube. The stringers shall be provided with a 3mm sponge rubber foam to provide sound absorbing buffer between the stringer and the panel. Finish: Galvanized steel. Connection: The stringer is screw fixed to the pedestal head forming a rigid under structure. A rigid grid system is used for FFH over 800mm
|
-
Specifications: