P: + 64 9 579 4799
E: sales@aspfloors.co.nz

Advanced Flooring Systems for buildings of the future

Steel Cementitious Ultrafix System

spec sc ultrafix system

 

Recommended Applications

recommended application sc ultrafix

 

SYSTEM NAME                             

Steel Cementitious Ultrafix System                                               

SYSTEM CODE                                  

SC-UF                                            

  

COMPLIANT STANDARDS                      
Australian Standard AS4154 / AS4155   

Australian Standard AS1170                  CISCA Standard UFGS - 09 69 11/15        

PSA MOB PF2 1992

NATA Testing Certification

IS09239 - 1 -2003

EN12825 - 2001

DIN4102- 1 -1998

 

DESCRIPTION                                                                

The Steel Cementitious Ultrafix System is the most commonly specified system used in most general office applications.
The system is used widely for power and data cable management.  

 

 

 

Specifiers Guide

sc ultrafix spec guide

 The adjacent table details how to nominate the ASP Ultrafix System in your project specification.

 

Access Floor Panel

 

sc ultrafix access floor panel

 

Type: SC Series - Steel Cementitious

Size: The panels are 600mm x 600mm in size and are interchangeable with other panels.

Also available are a series of load bearing finishing panels designed to minimise small off cuts experienced when cutting around columns, curved building designs and finishing off near perimeter walls. These finishing panels come in 600 x 800mm and 600 x 300mm sizes.

Depth: 33mm

Construction: The panels consist of a hardened steel top and bottom sheet plate with corrosion resistant protection, inside and out, encapsulating a structural cementitious core. 

Core: Cementitious Compound

Tolerance: ±0.25mm and a flatness tolerance of ±0.5mm measured on a diagonal across the top of the panel

Finish: ASP's standard powder coated finish.

Connection: The panel is screw fixed to the pedestal head at all four corners

 

Panel Load Tolerances  

AUSTRALIAN STANDARD (AS)

sc ultrafix aus standardSafety Factor: Panels must provide a minimum safety factor of 3 times the concentrated load specified above in accordance with AS4154-1993.

 

CISCA STANDARD

sc ultrafix CISCA STANDARD Safety Factor: Panels must provide a minimum safety factor of 5 times the uniform load specified above in accordance with ICC-ES AC300.

 

PSA MOB STANDARD

sc ultrafix PSA MOB STANDARD

 Safety Factor: Panels must provide a minimum safety factor of 3 times the concentrated load specified above in accordance with PSA MOB PF2 1992.

 

Access Floor Pedestals

 sc ultrafix access floor pedestal

sc ultrafix access floor pedestal 2

 

Size: 10,000mm² base plate  


Construction: Steel pedestal base and aluminium head assembly with a zinc electro­‐plated rod

 

Locking: The pedestals will be provided with an adjusting and locking nut to maintain the assembly at a selected height, which requires a deliberate action to change the height setting, and which prevents vibration displacement.    

 

Finish: ASP’s standard powder coated finish. 

 

Connection: 

The panel is screw fixed to the pedestal head at all four corners

 

Finished Floor Height (FFH): The finished floor height of the access floor is measured from the sub-floor to the top surface of the installed access floor.

 

sc ultrafix access floor pedestal 3