Steel Cementitious Air Tight System

spec sc air tight system

 

Recommended Applications

recommended application sc ultrafix

 

SYSTEM NAME                            

Steel Cementitious Air Tight System                                                  

SYSTEM CODE 

SC-AT                                                      

 

COMPLIANT STANDARDS 

Australian Standard AS4154 / AS4155   

Australian Standard AS1170   

CISCA Standard UFGS - 09 69 11/15

PSA MOB PF2 1992

NATA Testing Certification

IS09239 - 1 -2003

EN12825 - 2001

DIN4102- 1 -1998

 

DESCRIPTION    

The Steel Cementitious Air Tight System has been

designed to minimise air leakage when the access

floor is to be used as a plenum.

The system achieves this by incorporating the use

of a clip on air tight stringer that acts as a barrier in between the panels. 

 

Specifiers Guide

sc air tight spec guide

 The adjacent table details how to nominate the ASP Air Tight System in your project specification.

 

Access Floor Panel

 

sc air tight access floor panel

 

Type: SC Series - Steel Cementitious 

Size: The panels are 600mm x 600mm in size and are interchangeable with other panels.

Also available are a series of load bearing finishing panels designed to minimise small off cuts experienced when cutting around columns, curved building designs and finishing off near perimeter walls. These finishing panels come in 600 x 800mm and 600 x 300mm sizes.

Depth: 33mm

Construction: The panel consist of a hardened steel top and bottom sheet plate with corrosion resistant protection, inside and out, encapsulating a structural cementitious core.

Core: Cementitious Compound

Tolerance:  ±0.25mm and a flatness tolerance of ±0.5mm measured on a diagonal across the top of the panel

Finish: ASP's standard powder coated finish.

Connection: The panel is screw fixed to the pedestal head at all four corners

 

 

Panel Load Tolerances  

AUSTRALIAN STANDARD (AS)

sc air tight aus standardSafety Factor: Panels must provide a minimum safety factor of 3 times the concentrated load specified above in accordance with AS4154-1993.

 

CISCA STANDARD

sc air tight CISCA standard Safety Factor: Panels must provide a minimum safety factor of 5 times the uniform load specified above in accordance with ICC-ES AC300. 

 

PSA MOB STANDARD

sc air tight PSA MOB standard Safety Factor: Panels must provide a minimum safety factor of 3 times the concentrated load specified above in accordance with PSA MOB PF2 1992.

 

Access Floor Pedestals

 sc air tight access floor pedestal

sc air tight access floor pedestal 2 

 

Size: 10,000mm² base plate  


Construction: Steel pedestal base and aluminium head assembly with a zinc electro-­plated rod

 

Locking: The pedestals will be provided with an adjusting and locking nut to maintain the assembly at a selected height, which requires a deliberate action to change the height setting, and which prevents vibration displacement.    

 

Finish: ASP’s standard powder coated finish. 

 

Connection: 

The panel is screw fixed to the pedestal head at all four corners

 

Finished Floor Height (FFH): The finished floor height of the access floor is measured from the sub-floor to the top surface of the installed access floor.

 

sc air tight access floor pedestal 3 

 

Access Floor Stringers

 sc air tight access floor stringers

 

Type: AT Stringer

 

Size: 600mm

 

Construction: The Air Tight Stringer shall consist of 0.8mm thick steel, with a 3mm sponge rubber finish to act as a barrier in between the panels. 

 

Finish: Galvanized steel.

 

Connection: The AT Stringer clips into the AT cavity of the field pedestal to minimise the air leakage lost in between the panels.