Steel Cementitious HPL System

The SC HPL System is designed for those applications used for computer/data/comms/switch room applications incorporating a 1.6mm thick anti-static HPL covering. The HPL protects individuals from voltage shorts that can occur with electrical equipment on an access floor and also creates an electrostatic discharge which helps prevent buildup of the static electricity which can cause damage to the equipment. This system is recommended for applications such as:

  • IT Rooms
  • Comms Rooms
  • Switch Rooms
  • Data Centre

SC HPL system pic

 


design features

 

Gravity fixed panels:
Panels are gravity fixed to the understructure with stringers providing location and extra strength.


HPL Finish:
1.6mm high pressure laminate finish applied to panel in ASP standard finish. Custom and specialized HPL colours available upon request. The HPL panel is then finished with a brown edge, which is designed to eliminate panel chipping and delamination.

SC HPL System


Powder Coating, Nickel Platting and Hot Dipped Galvanized Stringers:
For specialised sensitive area such as clean rooms and data centres, ASP has introduced powder coated panels and pedestal tubes and base as well as nickel chrome platted pedestal head, threaded rod and nuts. The stringers are hot dipped galvanized. This specialized finish is available upon request.


Finishing Panels
Full bearing 600 x 300mm and 600 x 800mm panels designed to minimize small off cuts around columns and finishing off to perimeter. The 600 x 300 panel may also be used when there is a necessity for a 300m x 600mm air grille.

SC HPL System finishing panel 

 

SC HPL system understructure

 

Cementitious HPL S8 System
SC-HPL-RG S8 110-1200mm FFH

The SC HPL S8 system has been designed for applications with a FFH of 110-1200mm.
The pedestal tubes are manufactured or cut down to the appropriate length, and the steel thread rod is adjusted and locked at the desired height.

 

Understructure

• S8 Field / Perimeter Pedestal
• SC-S600 Stringer

SC HPL understructure1 

 

Cementitious HPL Heavy Duty S11 System
SC-HPL-RG S11 1200mm + FFH

The S11 System incorporates a thicker, sturdier heavy duty pedestal base and tube to suit seismic and FFH over 1200mm.

 

Understructure

• S11 Field / Perimeter Pedestal
• SC S600 Stringer

SC HPL understructure2 

 

S8 Field / Perimeter Pedestal

1. Pedestal Head and Welded steel thread rod
90x90mm steel flat head pedestal designed to provide a solid base for the panel. A 18mm by 150mm steel thread rod that is welded onto the bottom of the pedestal head with an adjustment range of 50mm +/- from FFH.

2. Adjusting and locking nut
Nut has an inbuilt vibration proof locking device, to ensure that once locked the pedestal height is static.

3. Pedestal Tube
Pedestal tube provides rigidity and stability to steel thread rod.

4. Pedestal Base
100x100mm pedestal base that provides a solid weight bearing platform for the access floor. Pedestal base has 4 fixing holes.

SC HPL understructure3

 

SC- S600 Stringer

1. Sponge Rubber
1.6mm thick sponge rubber to eliminate metal on metal noise transfer and assist with air leakage when sub floor is used as an air plenum.

2. Screw Holes
Pre-drilled screw holes to be used in conjunction with pedestal head to form a rigid grid understructure system.

3. Steel
1.4mm thick steel stringer, which provides greater stability and strength at the edges of the panel.

SC HPL understructure4 

 

 

SC HPL load tolerance 1 